Secondary Burden & Output Voltage
1-1. Super accuracy model
   
Application
 
0.2 Class watt hour meter for power station & substation.
Transformer operated & Indirect connected solid state energy meter for the high accuracy class.
Accuracy power transducer
Power sensor
Precision power meter
Power calibrator
Street lighting control system
   
Features
 
Super accuracy at the range of 0.25Amp or less
Zero phase displacement
Super linearity
   
General Specification
 
No problem with 1.2times continuous overload and 4 times overload for 1sec. against rated current being decided on the applied burden.
Dielectric withholding voltage : 3.5KV for 1 minute.
Humidity: Completely epoxy encapsulated & no humidity affected.
 
Standard Accuracy : 0.1 Class ( Meter )
   
Recommended Current Rating & Burden
 
Model Current Ratio Ratio Error Burden at 20 Current Rating
TZ106L/V, TZ79L 2,500/1 ±0.1% 0.5752VA 5Amp, 200Amp
TZ96L 5,000/1 ±0.1% 0.0957VA 5Amp, 200Amp
   
Drawing & Dimension
   
 
Drawing
   
 
   
 
Dimension ( unit : mm/inch )
 
Model A(min) B(max) C(max) D(max) E(max) F G H I(max)
TZ79L
TZ96L
19.4
0.764"
48.2
1.898"
19.3
0.760"
51.0
2.008"
12.2
0.480"
270±3
10.63"
5±1
0.197"
Rdc : 32-3 6
Rdc : 238-254
TZ106L
(A)
19.4
0.764"
48.2
1.898"
19.3
0.760"
51.0
2.008"
12.2
0.480"
270±3
10.63"
5±1
0.197"
Rdc
32-36
TZ106L
(B)
19.8
0.780"
48.2
1.898"
17.8
0.701"
52
2.047"
13.1
0.516"
270
10.630"
3
0.118"
TZ106V 18.5
0.728"
55.5
2.185"
20.3
0.799"
50.5
1.988"
30.0
1.181"
60±3
2.362"
4±0.5
0.157"
10±0.3
0.394"
67.6
2.661"
 
 